ROCOR NB
Liquid is the ideal corrosion inhibitor for closed heating or
cooling systems, such as diesel engines, compressors, process
cooling systems, etc.
Rocor NB
Liquid is a non-chromate, non-phosphate, free flowing liquid
that is extremely effective for controlling corrosion while
avoiding the pollution and toxicity problems associated with
chromate based inhibitors.
ADVANTAGES
* Controls
attack on piping, valves, pumps and heat exchangers by producing
a protective film on all exposed metal surfaces - iron, steel,
copper, copper alloys, aluminium and brass.
* Inherent Buffering agent automatically adjusts pH at the
preferred level.
* Does not adversely affect pump glands, rubber hose, water
seals, and valve packings.
* Prevents deposition of copper on ferrous surfaces by "tying
up" any copper which might be introduced. This eliminates the
possibility of attack caused when copper deposits on steel to
form galvanic cells or corrosion couples.
* Compatible with alcohol and glycol base antifreezes.
* Does not contain chromate or produce colour in the treated
water, thereby eliminating the possibility of stain.
* Liquid form simplifies usage and eliminates waste.
APPLICATION
Feed the
Rocor NB Liquid into any convenient point in the system with a
chemical proportioning pump or slug feed by using an appropriate
by-pass feeder. Rochem can supply suitable dosing equipment.
DOSAGE
Concentration level in the system must not be allowed to drop
below 1500 ppm as nitrite (N02). For economical reasons try to
maintain nitrite evel between 1500 ppm to 2000 ppm although
higher nitrite levels will not cause operating difficulties.
Nitrite level is obtained by using a simple colourimetric test
for nitrite.
DOSAGE TABLE
Nitrite
reading as ppm NO2 ROCOR NB Liquid required as ltrs per 1000
ltrs of water in system
0 - 300 14 Ltrs.
300 - 600 10 Ltrs.
600 - 900 8 Ltrs.
900 - 1200 5 Ltrs.
1200 - 1500 2 Ltrs
over - 1500 NONE
For example in untreated systems add 8.0 ltrs. of Rocor NB
Liquid for every 1000 litres of water in the system and check
(NO2) level with testkit after 4 hours. Adjust dosage as
required after regular intervals.
TESTING (PROCEDURE) Refer
to the Rochem technical date sheet for Nitrite testing.
TESTING (REMARKS)
* Use only cooling and feed water according to the requirements
of the motor anufacturer.
* Check pH of cooling water regularly - pH should be maintained
between 7.5 and 9.5.
* If the cooling water contains anti-freeze the above described
test is not reliable.
* To check for hardness, chlorides, and pH, refer to the Rochem
Technical Date sheet for Cooling Water tests.
CAUTION
Wear rubber gloves and
avoid contact with skin and eyes when handling Rocor NB Liquid.
In case of contact, immediately flush skin and eyes with water
for 15 minutes. Get medical attention |